Check snmp¶
Overview¶
Queries SNMP OIDs defined in a CSV file and checks the returned values against optional warning and critical thresholds. Supports SNMP v1, v2c, and v3 with authentication and privacy protocols.
Important Notes:
-
SNMP is a dated and comparatively complex protocol. Use it only as a last resort, when you can neither run an agent on the target nor reach it through a good API:
- If you can use an agent of your monitoring software (e.g. Icinga) together with one of our plugins, do that.
- If you cannot install an agent but the device offers a good (REST) API, use the API.
- If you can neither install an agent nor reach a good API (typical for switches, PDUs, UPS units, printers or sensors), fall back to SNMP.
- For a pure SNMP estate, consider a specialized solution like LibreNMS instead of this check.
-
SNMPv2c is widely used because it is simple, but its community string travels in cleartext. Prefer SNMPv3 where the device supports it, and restrict v2c to trusted, read-only management networks.
- This check sends targeted
snmpgetrequests for a defined OID list, which is light on the device. Broad SNMP walks are what put real load on hardware, and this check avoids them. The OID list is split automatically into blocks of 25 OIDs per request. - If you acknowledge a value change in Icinga, the desired WARN or CRIT state remains. Delete
$TEMP/linuxfabrik-monitoring-plugins-snmp.dbto reset the inventory.
Data Collection:
- Reads OID definitions from a CSV file in the
device-oidsdirectory (default:any-any-any.csv) - Calls
snmpgetin blocks of 25 OIDs per request to avoid "tooBig" errors - Supports re-calculation of values, custom units, human-readable formatting (bytes, seconds, bps), and computed values using Python expressions
- Values can be shown in the first output line, filtered from the table, or excluded from perfdata
Fact Sheet¶
| Fact | Value |
|---|---|
| Check Plugin Download | https://github.com/Linuxfabrik/monitoring-plugins/tree/main/check-plugins/snmp |
| Nagios/Icinga Check Name | check_snmp |
| Check Interval Recommendation | Every 5 minutes |
| Can be called without parameters | No (--hostname is required) |
| Runs on | Cross-platform |
| Compiled for Windows | No |
| Requirements | snmpget from net-snmp-utils |
| Uses SQLite DBs | $TEMP/linuxfabrik-monitoring-plugins-snmp.db |
Help¶
usage: snmp [-h] [-V] [--community COMMUNITY] [--device DEVICE] [--hide-ok]
[--hide-table] -H HOSTNAME [--mib MIB] [--mib-dir MIB_DIR]
[--snmp-version {1,2c,3}] [-t TIMEOUT]
[--v3-auth-prot {MD5,SHA,SHA-224,SHA-256,SHA-384,SHA-512}]
[--v3-auth-prot-password V3_AUTH_PROT_PASSWORD]
[--v3-boots-time V3_BOOTS_TIME] [--v3-context V3_CONTEXT]
[--v3-context-engine-id V3_CONTEXT_ENGINE_ID]
[--v3-level {noAuthNoPriv,authNoPriv,authPriv}]
[--v3-priv-prot {DES,AES,AES-192,AES-256}]
[--v3-priv-prot-password V3_PRIV_PROT_PASSWORD]
[--v3-security-engine-id V3_SECURITY_ENGINE_ID]
[--v3-username V3_USERNAME]
Queries SNMP OIDs defined in a CSV file and checks the returned values against
optional warning and critical thresholds. Supports SNMP v1, v2c, and v3 with
authentication and privacy protocols.
options:
-h, --help show this help message and exit
-V, --version show program's version number and exit
--community COMMUNITY
SNMP v1/v2c community string. Default: public
--device DEVICE CSV file containing the SNMP OIDs. A bare filename is
looked up under the bundled `./device-oids` directory.
An absolute path loads a CSV from anywhere on the
filesystem, so the OID definitions can live outside
the plugin directory. The recommended naming
convention is `class-vendor-model.csv`. `any-any-
any.csv` is a good starting point showing some
features. The file is trusted input: its recalculation
and threshold fields are evaluated as Python
expressions, so it must be writable only by trusted,
privileged users. The monitoring user (for example
`icinga` or `nagios`) only needs read access. Example:
`--device switch-fs-s3900.csv`. Example: `--device
/etc/icinga2/snmp-devices/switch-fs-s3900.csv`.
Default: any-any-any.csv
--hide-ok Suppress OIDs with OK state from output. Default:
False
--hide-table Suppress the table from output. Default: False
-H, --hostname HOSTNAME
SNMP appliance hostname or IP address.
--mib MIB MIB(s) to load, behaves like the `-m` option of
`snmpget`. Example: `--mib "+FS-MIB"` or `--mib "FS-
MIB:BROTHER-MIB"`.
--mib-dir MIB_DIR Colon-separated list of directories to search for
MIBs, behaves like the `-M` option of `snmpget`.
Default: $HOME/.snmp/mibs:/usr/share/snmp/mibs
--snmp-version {1,2c,3}
SNMP version to use. Default: 2c
-t, --timeout TIMEOUT
Network timeout in seconds. Default: 7 (seconds)
--v3-auth-prot {MD5,SHA,SHA-224,SHA-256,SHA-384,SHA-512}
SNMPv3 authentication protocol.
--v3-auth-prot-password V3_AUTH_PROT_PASSWORD
SNMPv3 authentication protocol passphrase.
--v3-boots-time V3_BOOTS_TIME
SNMPv3 destination engine boots/time.
--v3-context V3_CONTEXT
SNMPv3 context name. Example: `--v3-context bridge1`.
--v3-context-engine-id V3_CONTEXT_ENGINE_ID
SNMPv3 context engine ID. Example: `--v3-context-
engine-id 800000020109840301`.
--v3-level {noAuthNoPriv,authNoPriv,authPriv}
SNMPv3 security level.
--v3-priv-prot {DES,AES,AES-192,AES-256}
SNMPv3 privacy protocol.
--v3-priv-prot-password V3_PRIV_PROT_PASSWORD
SNMPv3 privacy protocol passphrase.
--v3-security-engine-id V3_SECURITY_ENGINE_ID
SNMPv3 security engine ID. Example: `--v3-security-
engine-id 800000020109840301`.
--v3-username V3_USERNAME
SNMPv3 security name (username). Example:
`--v3-username bert`.
Usage Examples¶
A minimal command call:
./snmp --hostname 10.80.32.109
Calling this the check...
- fetches a set of most common SNMP OIDs like Contact or Uptime, defined in
device-oids/any-any-any.csv, - calls
snmpget -v 2c -c public -r 0 -t 7 -OSqtU -M $HOME/.snmp/mibs:/usr/share/snmp/mibs 10.80.32.109 OID1 OID2 ..., - parses the output,
- interprets the result and calculates the return state.
Other example using a more specific OID list and an additional MIB directory:
/usr/lib64/nagios/plugins/snmp \
--device switch-fs-s3900.csv \
--mib-dir +/usr/lib64/nagios/plugins/device-mibs/switch-fs-s3900 \
--hide-ok \
--hostname 10.80.32.109
Checking a Radware Alteon load balancer appliance - CSV file and result:
OID,Name,Re-Calc,Unit Label,WARN,CRIT,Show in 1st Line,Report Change as
SNMPv2-SMI::enterprises.1872.2.5.1.2.8.1.0,TotalMem,int(value),,,,,
SNMPv2-SMI::enterprises.1872.2.5.1.2.8.3.0,FreeMem,int(value),,,,,
,warnPercent,70,%,,,,
,critPercent,90,%,,,,
,UsedMem,"values['TotalMem'] - values['FreeMem']",,,,,
,Memory Usage,"round( 100.0 * values['UsedMem'] / values['TotalMem'],2)",%,value > values['warnPercent'],value > values['critPercent'],True,
lb-alteon-any.csv: Memory Usage: 40.06%
Key ! Value ! State
-------------+----------+-------
TotalMem ! 65835992 ! [OK]
FreeMem ! 39465220 ! [OK]
warnPercent ! 70% ! [OK]
critPercent ! 90% ! [OK]
UsedMem ! 26370772 ! [OK]
Memory Usage ! 40.06% ! [OK]
Installation¶
Install snmpget:
# on RHEL:
yum -y install net-snmp-utils
# on Debian:
apt -y install snmp snmp-mibs-downloader
Plugin Directory Structure¶
/usr/lib64/nagios/plugins/
├── device-mibs
│ ├── printer-...
│ ├── ...
│ └── switch-...
└── device-oids
Handling MIBs¶
If needed, get any MIB files ready. Copy them to $HOME/.snmp/mibs or /usr/share/snmp/mibs. If you prefer other locations, provide the paths using the --mib-dir parameter (same syntax as the -M parameter of snmpget). The check comes with some predefined, device-dependent MIBs located at /usr/lib64/nagios/plugins/device-mibs/.
Create an OID list in /usr/lib64/nagios/plugins/device-oids/... using CSV format. For details, have a look at "Defining a Device" within this document.
Defining a Device via CSV file¶
If you want to define a device-specific list of OIDs, including any calculations, warning and critical thresholds, create a CSV file located at device-oids, using , as delimiter and " as quoting character. Pass a bare filename to --device to load it from the bundled device-oids directory, or an absolute path to load it from anywhere on the filesystem (for example --device=/etc/icinga2/snmp-devices/switch-fs-s3900.csv). Because the Re-Calc and threshold columns are evaluated as Python expressions, the file must be writable only by trusted, privileged users; the monitoring user (for example icinga or nagios) only needs read access. A minimal example for nearly any device:
| OID | Name | Re-Calc | Unit Label | WARN | CRIT | Show in 1st Line | Report Change as | Ignore in Perfdata | Perfdata Alert Thresholds | Skip Output |
|---|---|---|---|---|---|---|---|---|---|---|
| SNMPv2-MIB::sysName.0 | Name | |||||||||
| SNMPv2-MIB::sysLocation.0 | Location | WARN | True | |||||||
| SNMPv2-MIB::sysUpTime.0 | Uptime | int(value) / 100 * 24*3600 | s | value > 6*30 | value > 2*365 | True | "3*30,None" |
The columns in detail:
-
OID: String. The Object-Identifier from any of your MIB files.
-
Name: String. If provided, the check prints this instead of the OID.
-
Re-Calc: Python code, or empty. Feel free to use any Python code based on the variables
valueandvalues, which contain the result (always a string) of the SNMPGET operation on the given OID. -
Unit: String, or empty. This is the "Unit of Measurement", case-insensitive. One of:
- s - seconds (also us, ms)
- % - percentage
- B - bytes (also KB, MB, TB, ...)
- bps - bits per second (also Kbps, Mbps, ...)
- c - a continuous counter (such as bytes transmitted on an interface)
If you provide two comma-separated units, for example "b,c", the first one will be used to display a human-readable format ("Bytes"), and the second one is used to suffix the perfdata ("continuous counter"). For output, the following units will always be converted to a human-friendly format:
* s - seconds
* b - bytes
* bps - bits per second
-
WARN: Python condition, or empty. The warning condition for the re-calculated or raw
value. -
CRIT: Python condition, or empty. The critical condition for the re-calculated or raw
value. -
Show in first line: Bool, either "False", "True", or empty. Should
valuebe printed in the first line of the check output? -
Report Change as: String, either "WARN", "CRIT", or empty. Should a change of
valuebe reported asWARNorCRIT? The check stores the initial values on the first run in$TEMP/linuxfabrik-monitoring-plugins-snmp.db. -
Ignore in Perfdata: Bool, either "False", "True", or empty. By default, all numeric values are automatically returned as perfdata objects. Set to
Trueto exclude this item from the perfdata list. -
Perfdata Alert Thresholds: Python tuple, or empty. The "WARN" and "CRIT" columns hold Python conditions (for example
value > 80), not plain numbers, so they cannot be written into the performance data as-is. This column provides the numeric thresholds (and optionally the graph axis bounds) that should appear in the perfdata, as a Python tuple of two to four elements:warn,critorwarn,crit,min,max. The first element is the warning threshold, the second the critical threshold, and the optional third and fourth pin the minimum and maximum of the graph axis. UseNonefor "no value". When min and max are omitted, they default to0and (for percentages)100, otherwise to no maximum. Wrap the tuple in double quotes, otherwise the commas inside it are read as CSV field separators. Examples:"3*30*24*3600,5*365*24*3600"and"26,28,0,50". A non-empty entry that is not such a tuple is reported as UNKNOWN, so a typo does not silently drop the thresholds.
This column only annotates the performance data, meaning the warn, crit, min, and max fields a graphing tool draws. It has no effect on the OK, WARN, or CRIT state the plugin returns; that state is decided solely by the "WARN" and "CRIT" columns. Because the two are independent, the values here may differ from the conditions in "WARN" and "CRIT". Normally you keep them in sync by repeating the same numeric breakpoints. A row can also have perfdata thresholds without any "WARN"/"CRIT" condition, purely for visualization.
The repetition looks redundant but the separation is deliberate and buys you flexibility: the "WARN" and "CRIT" columns may hold arbitrary Python conditions, including comparisons that combine several OIDs or that have no single numeric equivalent, while the perfdata still gets clean numeric threshold lines a graphing tool can draw. It also lets you place a guideline at a value that differs from the alerting threshold, or annotate a metric that is not alerted on at all.
- Skip Output: Bool, either "False", "True", or empty. Should this row be included in the resulting table output? Set this to "True" if you only need the row for calculations.
Calculating and Comparing using value and values¶
value contains the value of the current OID, simply and always as a Python string. values is a Python dictionary containing all re-calculated (or raw) values, up to this point. The dictionary keys are based on the "Name". If "Name" is not set, the dictionary keys are based on the "OID".
The value returned by snmpget for a given OID is always a string. If you want to use it for calculations or integer-based comparisons, re-calculate it by specifying int(value) in the column (SNMP knows nothing about floats).
Some devices return numeric readings wrapped in double quotes, for example "9.82". Then int(value) or float(value) fails with could not convert string to float: '"9.82"'. Strip the quotes first inside the Re-Calc column:
| OID | Name | Re-Calc | Unit Label | WARN | ... |
|---|---|---|---|---|---|
| ENTITY-SENSOR-MIB::entPhySensorValue.1 | Voltage | float(value.strip('"')) | V | value > 12.6 |
Both variables are allowed to be used in Python code in the columns "Re-Calc", "WARN" and "CRIT". This enables you to even warn in the current OID depending on previous values, for example.
In the last three lines of this example we simply calculate "NIC.1 Traffic" as a sum of "NIC.1 rx" and "NIC.1 tx", for which there is no SNMP OID:
| OID | Name | Re-Calc | Unit Label | WARN | ... |
|---|---|---|---|---|---|
| SNMPv2-MIB::sysUpTime.0 | Uptime | int(value) / 100 | s | value > 4*365*24*3600 | |
| IF-MIB::ifSpeed.1 | NIC.1 Speed | int(value) | bps | ||
| IF-MIB::ifOperStatus.1 | NIC.1 Status | ||||
| IF-MIB::ifOutOctets.1 | NIC.1 tx | int(value) | b,c | ||
| IF-MIB::ifInOctets.1 | NIC.1 rx | int(value) | b,c | ||
| \<leave this empty> | NIC.1 Traffic | values['NIC.1 tx'] + values['NIC.1 rx'] | b,c |
Parameter Mapping snmpget vs. this Plugin¶
snmpget |
This check |
|---|---|
-v 1|2c|3 |
--snmp-version {1,2c,3} |
-c COMMUNITY |
--community COMMUNITY |
-a PROTOCOL |
--v3-auth-prot {MD5,SHA,SHA-224,SHA-256,SHA-384,SHA-512} |
-A PASSPHRASE |
--v3-auth-prot-password V3AUTHPROTPASSWORD |
-e ENGINE-ID |
--v3-security-engine-id V3SECURITYENGINEID |
-E ENGINE-ID |
--v3-context-engine-id V3CONTEXTENGINEID |
-l LEVEL |
--v3-level {noAuthNoPriv,authNoPriv,authPriv} |
-n CONTEXT |
--v3-context V3CONTEXT |
-u USER-NAME |
--v3-username V3USERNAME |
-x PROTOCOL |
--v3-priv-prot {DES,AES,AES-192,AES-256} |
-X PASSPHRASE |
--v3-priv-prot-password V3PRIVPROTPASSWORD |
-Z BOOTS,TIME |
--v3-boots-time V3BOOTSTIME |
-r RETRIES |
hard-coded to 0 |
-t TIMEOUT |
-t TIMEOUT, --timeout TIMEOUT |
-m MIB[:...] |
--mib MIB |
-M DIR[:...] |
--mib-dir MIBDIR |
How to fetch a list of OIDs¶
Example:
snmpbulkwalk -v2c \
-c public \
-OSt \
-M +/usr/lib64/nagios/plugins/device-mibs/switch-netgear-xs716t \
10.80.32.141 NETGEAR-SWITCHING-MIB::agentInfoGroup
States¶
- OK, WARN, CRIT, or UNKNOWN depending on the OID definitions in the CSV file.
- UNKNOWN if an OID returns "No Such Instance" or "No Such Object".
- UNKNOWN if a Re-Calc expression fails.
Perfdata / Metrics¶
By default, all numeric values are automatically returned as perfdata objects. Use the "Ignore in Perfdata" CSV column to exclude specific items. The warn and crit threshold fields in the perfdata come from the "Perfdata Alert Thresholds" CSV column and are purely for visualization; they do not influence the plugin's state.
| Name | Type | Description |
|---|---|---|
| \<oid-label> | Number | Value of the queried OID. Labels and thresholds are defined in the CSV file. |
Troubleshooting¶
IndexError: list index out of range¶
Something is wrong with your CSV file format. Try editing it in LibreOffice Calc, for example, to get the right amount of commas, quotes, etc.
Too many object identifiers specified. Only 128 allowed in one request.¶
Probably your SNMP v3 parameters are incomplete or incorrect.
MIB index file too large¶
add_mibdir: strings scanned in from .snmp/mibs/.index are too large. count = ...
There seems to be a malformed, a duplicated MIB file or one with spaces in its filename within one of your MIB directories.
Error in packet. Reason: (tooBig) Response message would have been too large.¶
A "tooBig" response simply means that the SNMP agent tried to generate a response with all requested OIDs, but the response grew too big for its buffer, resulting in this error message. The check already limits requests to a maximum of 25 OIDs each.
Does an acknowledged value change return to OK?¶
If you acknowledge a value change in Icinga, the desired WARN or CRIT state remains, because SNMP is mostly run against hardware and you have to check what triggered the change. If everything is fine, delete $TEMP/linuxfabrik-monitoring-plugins-snmp.db. On the next run, the plugin will recreate the inventory.